A wet patch under a radiator valve is one of the most common plumbing complaints and one of the easiest to deal with, provided you work out where the water is actually coming from first.
Find the source before doing anything
Dry the whole valve and the pipe completely with a cloth.
Wrap a dry piece of kitchen roll or toilet tissue around each joint in turn and leave it for an hour.
The one that goes damp tells you the source, and there are only three realistic candidates.
The gland nut, which is the nut just below the valve head or handle. This is the most common, and the easiest.
The union nut, the large nut connecting the valve body to the radiator tail.
The compression joint where the valve meets the pipe from the floor or the wall.
Water running down the pipe from above can also come from the radiator itself or from a joint higher up, which is why drying everything first matters.
A leaking gland nut
This is the fix that takes ten minutes and needs no draining.
The gland nut compresses a packing or an O ring around the valve spindle. Over time that packing hardens and lets water weep out around the spindle.
Turn the valve fully off first.
Tighten the gland nut a quarter turn with a small spanner while holding the valve body with a second spanner.
Dry it off and watch. Frequently that is the whole repair.
If it still weeps, undo the gland nut fully, lift it up the spindle, and wrap PTFE tape around the spindle underneath it, pushing the tape down into the recess with a small screwdriver. Retighten and test.
A leaking union nut
The union nut connects the valve to the tail screwed into the radiator, and it seals on a tapered face or an O ring.
Try tightening it a quarter turn first, holding the valve body with a second spanner so the pipework is not twisted.
Do not overtighten. These are compression seals, not threads to be forced, and overtightening distorts the seal and makes the leak worse.
If tightening does not work, the joint has to come apart, which means draining the radiator.
Draining down
Turn both valves off: the wheel head or thermostatic valve one side, and the lockshield the other.
Count the turns as you close the lockshield and write the number down, so the system balance can be restored afterwards.
Put a shallow tray and towels underneath, and have a bucket ready.
Open the bleed valve at the top to let air in, then slowly undo the union nut and let the water out. Radiator water is black and stains carpet permanently, so protect generously.
Remaking the joint
Clean the tapered face and the O ring seat.
Replace the O ring if there is one, or wrap PTFE tape around the tail thread in the direction of tightening.
Some fitters use a smear of jointing compound over PTFE on these joints, which is acceptable on a heating system.
Reassemble hand tight, then a quarter turn with a spanner.
Refill, bleed the radiator and check thoroughly before putting furniture back.
A leaking compression joint at the pipe
Try a quarter turn first.
If that fails, drain down, undo the joint and inspect the olive. A distorted or scored olive will not seal again, and removing one without damaging the pipe is fiddly.
An olive puller does it cleanly. Cutting the pipe back and fitting a new olive is the alternative where there is enough length.
When the valve needs replacing
Where the body is corroded, cracked or weeping from the casting rather than a joint.
Where a thermostatic head has failed and the pin is stuck.
Where the valve will not shut off, which makes every other repair impossible.
Replacing a valve means draining that part of the system, and on an older system the tail may be seized into the radiator.
Refilling and pressure
On a sealed system, top up through the filling loop and watch the pressure gauge, aiming for the figure marked on the boiler, commonly around one bar when cold.
Bleed every radiator in the house afterwards, working upwards, then check the pressure again.
Reopen the lockshield by the number of turns you counted.
Leave towels in place for a day and check again once the system has heated and cooled, since joints move as they expand.