Replacing a light switch is straightforward provided you understand one thing: the conductors at a switch are all lives. There is normally no neutral in a switch box.
The key point
A switch interrupts the live feed to a light. The cable running down from the ceiling carries a permanent live down and a switched live back up.
Twin and earth has only two insulated conductors, so the blue, or black in older cable, is pressed into service as the switched live and should be sleeved brown or red at both ends.
A blue conductor in a switch box is live. Sleeved or not.
Before starting
- Not in a bathroom. Work in a room containing a bath or shower is notifiable everywhere in the UK. Bathroom switching is normally a ceiling pull cord or a switch outside the door
- Check the existing switch and wiring are sound before deciding to proceed
- Where there is no earth conductor, do not fit a metal switch
What you need
- A matching replacement switch, with the right number of gangs and ways
- Insulated screwdrivers
- An approved voltage indicator and a proving unit
- An MCB lock-off device
- Brown sleeving and green and yellow earth sleeving
- A camera, a torch and some labels
Step 1: isolate and prove dead
- Turn off the lighting circuit breaker, not the socket circuit
- Lock it off and tell everyone
- Confirm the light does not work
- Remove the switch plate screws and ease the plate forward
- Prove dead across every combination of conductors, using prove, test, prove
On a two-way switch, the light can be fed from two directions. Isolating one circuit may not make both safe. Prove every conductor.
Step 2: photograph and identify
Photograph the back of the plate clearly, then work out which arrangement you have.
One-way switch, one cable:
- Terminals marked COM and L1, or just two terminals
- Brown to COM, blue sleeved brown to L1
- Earth to the box or the plate
Two-way switch, two switches controlling one light:
- Three-core and earth between the two switches
- Terminals COM, L1 and L2
- Brown to COM, black and grey to L1 and L2, both sleeved brown
- The two switches must be wired consistently
Intermediate switch, three or more switches on one light:
- Four terminals
- Wired between two two-way switches
- More involved; photograph carefully and replace like for like
Multi-gang switch: each gang has its own COM and L1, controlling a separate light. Label which is which before disconnecting.
Step 3: sleeving
- Every blue or black conductor used as a switched live must be sleeved brown, or red in an older installation
- Every bare earth must be sleeved green and yellow for its exposed length
- Where the existing sleeving is missing, add it
Step 4: earthing
- Plastic switch on a plastic box: the earth is connected to the plate's earth terminal, or parked safely if the plate has none. It must not be cut off
- Metal switch on a metal box: earths to the plate, plus an earth flylead from the box terminal to the plate
- No earth in the cable at all: common in older lighting circuits. Fit a plastic switch only, and consider having the circuit assessed
Step 5: connect and fit
- Connect each conductor to the same terminal it came from, per your photograph
- Insert fully, tighten firmly, and tug each to check
- Fit the earth flylead if the box is metal
- Fold the conductors back carefully without trapping them
- Fit the plate square and tighten evenly
- Remove the lock-off and restore power
- Test all switches, including the two-way from both positions
Fitting a dimmer
Worth extra care.
- The dimmer must be compatible with the lamps. Most modern dimmers are for LED, and an old resistive dimmer will make LEDs flicker, buzz or not dim at all
- Check the dimmer's minimum and maximum load. A single LED lamp may be below the minimum
- Check the lamps themselves are marked dimmable. Non-dimmable LEDs will flicker and fail early
- A two-way circuit needs a dimmer designed for two-way, and only one of the two switches can be the dimmer
- Dimmers are deeper than plate switches, so check the box depth
Smart switches
Many require a permanent neutral at the switch, which most UK switch boxes do not have.
Check the requirement before buying. Some models work without a neutral, and they can be fussy about the load.
If it goes wrong
Light does not work after replacing: isolate and check against your photograph.
Two-way switching not working correctly: the strappers are on the wrong terminals. Isolate and swap L1 and L2 at one switch.
LEDs flickering after fitting a dimmer: incompatible dimmer or non-dimmable lamps.
No earth in the box: fit a plastic switch and get the circuit assessed.
Blue conductor with no sleeve: assume it is live, sleeve it brown, and treat with care.
A summary
- Everything in a switch box is a live conductor, whatever colour it is
- Isolate the lighting circuit, lock off, and prove dead across every combination
- Photograph and label before disconnecting
- Sleeve switched lives brown and earths green and yellow
- No earth in the box means a plastic switch only
- Check dimmer compatibility with the lamps before buying
Choosing the replacement
- Count the gangs, the number of rockers, and match it
- Establish whether each gang is one-way or two-way. A two-way switch can be used as one-way; the reverse cannot
- Check the box depth, since deeper plates and dimmers need more room behind
- Match the plate size to the existing box, usually a single or double module
- For a metal plate, confirm there is an earth in the box first